POWER SOURCE FOR ELECTRON BEAM MELTING
Upto 15kW
IONICS has designed, developed and supplied regulated power supplies for Electron Beam Melting equipment using the transformer-rectifier topology.
PARAMETER | SPECIFICATION |
---|---|
Input Voltage | 415V ±10% A C, 50Hz, three phase |
Ambient temperature | 40˚C |
Method of cooling | Air-cooled |
Type of Transformer | Epoxy cast dry type rectifier transformer |
Duty | Continuous operation |
Installation | Indoor |
Protections | Input HRC fuses Single phasing preventer Harmonic filter at the mains input Thermal overload relays Linear reactor for limiting short circuit current |
Digital Monitoring | Acceleration voltage - 0 to -15kV DC average Beam current - 0 to 1A DC mean |
Controls & Signals on Control Panel | Push buttons for ON/ OFF 10 turn potentiometer for voltage, current control LED indications for ON/ OFF, fault status |
Construction | The unit is to be divided into three parts viz., The transformer cubicle, control cubicle and control console |
ACCELERATIO N VO LTAGE SUPPLY | |
Output Voltage Range | -0.5kV DC to -15kV DC average |
Output Current Range | 0 to 1A mean |
Line Regulation | Upto 4% for 10% variation in input voltage |
Load Regulation | Upto 4% for 0 to 100% load variation |
Stability | < 10% |
Ripple at frequencies ≤ 1 kHz | Upto 4% rms of set value – within working range |
Resolution | 0.5kV for voltage and 10mA for current |
Protections* | Against over load, over current, over voltage, over watts and short -circuit. During short circuit power supply trips |
FILAMENT HEATING SUPPLY (EHT INSULATED) | |
Output Voltage Range | 0 to 7V AC rms |
Output Current Range | 0 to 40A |
Insulation Level | This supply will be floating at -15kV DC |
Protections | The power supply will incorporate trip circuit for over current fault. |
Topology | Thyristorised primary controller followed by single phase step down transformer, independent close loop control |
FOCUSING SUPPLY | |
Output Voltage Range | Upto 70V DC |
Output Current Range | 0 to 1A |
Ripple | ≤ 0.1% |
Resolution | 1mA |
BEAM OSCILLATIO N SUPPLIES (X & Y) 2 SETS | |
Output Voltage Range | 0 to 10V A C sinusoidal |
Output Current Range | 0 to 1A (max) continuously variable by multi-turn potentiometer. |
Frequency | Variable from 3Hz to 50Hz, sinusoidal and saw tooth with selector switch |
Phase Shift* | Adjustable phase shift of 0 – 180˚ between the two sets of output |
Line Regulation | Upto 0.1% for 10% variation in input voltage |
Load Regulation | Upto 0.1% |
BEAM DEFLECTIO N SUPPLIES (X & Y) 2 SETS | |
Voltage | 0 to 5V DC |
Current | 0 to 0.5A (max) continuously variable by multi turn potentiometer. |
Polarity | Positive / negative (selectable through switch) |
Line Regulation | Upto 0.1% for all changes in line voltage of ±10% |
Load Regulation | Upto 0.1% |
Ripple | < 1mV rms |
*Optional. To be specified by the user.